Voltech logo
    • Login
  • Welcome
  • Applications
  • Products
  • Support
  • Contact Us
Voltech logo
  • Welcome
  • Applications
  • Products
  • Support
  • Contact Us
Contact Voltech
USA 1-239-437-0494
EUR 44 1235 861173
ASIA 44-1235-364-001
or
Email Voltech
Voltech on LinkedIn Voltech on YouTube Voltech on Twitter
    • Login
Technical Document Reader
Document
086-627
Name

The Voltech Handbook of Transformer Testing

Description
This article covers a wide range of transformer theory and Voltech's testing capability.
The Voltech Handbook of Transformer Testing
Back
to Index
Skip Navigation Links.
Expand 1 Transformer Basics1 Transformer Basics
Collapse 2 Available Tests2 Available Tests
2.1 CTY - Continuity
2.2 R - Winding Resistance
2.3 RLS or RLP - Equivalent Series or Parallel R
2.4 LS_LP - Primary Inductance
2.5 LSB_LPB - Inductance With Bias Current
2.6 QL - Q factor
2.7 D - Dissipation Factor
2.8 LL - Leakage Inductance
2.9 C - Inter-winding Capacitance
2.10 TR - Turns Ratio and Phasing
2.11 TRL - Turns Ratio by Inductance
2.12 Z_ZB - Impedance_Impedance with Bias
2.13 R2 - DC Resistance Match
2.14 L2 - Inductance Match
2.15 C2 - Capacitance Match
2.16 GBAL - General Longitudinal Balance
2.17 LBAL - Longitudinal Balance
2.18 ILOS - Insertion Loss
2.19 RESP - Frequency Response
2.20 RLOS - Return Loss
2.21 ANGL - Impedance Phase Angle
2.22 PHAS - Inter-winding Phase Test
2.23 TRIM - Trimming Adjustment
2.24 OUT - Output To User Port
2.25 IR - Insulation Resistance
2.26 HPDC - DC HI-POT
2.27 HPAC - AC HI-POT
2.28 SURG - Surge Stress Test
2.29 STRW - Stress Watts
2.30 MAGI - Magnetizing Current
2.31 VOC - Open Circuit Voltage
2.32 WATX - Wattage (External Source)
2.33 STRX - Stress Watts (External Source)
2.34 MAGX - Magnetizing Current (Ext. Source)
2.35 VOCX - O.C. Voltage (External Source)
2.36 LVOC - Low Voltage Open Circuit
2.37 ILK - Leakage Current
2.38 LSBX - Inductance with External Bias (Series)
2.39 LPBX - Inductance with External Bias (Parallel)
2.40 ZBX - Impedance with External Bias
2.41 ACRT - AC HI-POT Ramp
2.42 DCAT - DC HI-POT Ramp
2.43 ACVB - AC Voltage Break Down
2.44 DCVB - DC Voltage Break Down
2.45 WATT - Wattage
2.0 Available Tests On The AT Series
Expand 3 Examples of Different Transformer Types3 Examples of Different Transformer Types

2.25 IR - Insulation Resistance


Transformer windings are often insulated from each other and from the core by insulating tape, enamel on the wire or by plastic moulding on the bobbin.

The quality of the insulation can be assessed by applying a DC voltage across the insulation and measuring the value of resistance.

The voltage applied is usually greater than the voltage that the insulation will see in normal use.

Typical test voltage is 200V to 500V DC, and the insulation resistance expected will be of the order of one hundred to several thousand MOhms.

Where Used

An Insulation Resistance check is recommended as good practice for most transformers to check the integrity of the insulation between separate windings, or between a winding and a screen.

It is used where winding isolation is a part of the functionality of the transformer, but not part of a safety requirement, for which a Hi-Pot (EHT) test is preferred.

It would therefore be used, for example, between two primary windings, or between two secondary windings.

Measurement Conditions

To measure insulation resistance, the tester applies a dc voltage between two groups of windings, with the windings in each group being shorted together. Each group may contain as many windings as you wish.

The voltage and current are measured; dividing the voltage by the current gives the insulation resistance.

You can also command the tester to perform a compensation measurement on the empty fixture at the start of a test run. This is recommended as it will allow the tester to subtract the errors due to the fixture from subsequent measurements, to give more accurate results.

The test voltage may be chosen in the range from 100V to 7kV. (500V AT1600).

Normally however, you would perform the test with a voltage just greater than twice the highest possible peak working voltage on the winding. Therefore, for example, to check the isolation between the two primary windings of a line frequency transformer, which could be connected in series and operated at 240V, 800V would be a suitable test signal.


Prev Next
Email Voltech
USA 1-239-437-0494
EUR 44 1235 861173
ASIA 44-1235-364-001
Site Map
Terms Of Business
Terms Of Use
Privacy
  • Terms Of Use
  • Privacy
  • Terms Of Business
  • Site Map
Contact Voltech
USA 1-239-437-0494
EUR 44 1235 861173
ASIA 44-1235-364-001
or
Email Voltech
 
Submit "Red" = required field
Please, complete all required fields.
Please, select country from the list.
Please, enter a valid Email.
Thank you for your question. We will reply to your request as soon as possible.
An error occurred.
Voltech © 2021
Voltech on LinkedIn Voltech on YouTube Voltech on Twitter
We have placed cookies on your computer to help make this website better.
Please read our Privacy Statement for further information. Otherwise, we'll assume you're OK to continue.
OK, Don't Show This Message Again